Web Server for BACnet
Model AMJR-14-BN
Alarm Monitoring
Time & Date Scheduling
Data Logging
Email Notifications
User Defined Web Pages
12 Analog/Universal Inputs
2 Discrete Outputs
Modbus RTU Master Gateway
BACnet IP Client & Server
|
|
 |
The BACnet version of the i.CanDoIt® server features a BACnet IP client and server. This server is ideal I/O add-on or stand alone controller for a BACnet IP system. The i.CanDoIt® BACnet controller is freely programmable.
Control Solutions’ i.CanDoIt® AddMe Jr. features 12 inputs which accept analog input from thermistors or 0-10V sensors, or discrete input from dry contact switches. Model AMJR-14 also provides 2 discrete ouputs which can sink 1A at 24VDC.
Analog data is available via Analog Input objects. Linearization tables are provided for 10K and 20K type II, III, and IV thermistors on analog inputs. Input and output type and scaling are configured in web pages served by the internal web server. Outputs are accessed via commandable Binary Output objects. Additional uncommitted writeable Analog Input objects, plus writeable Multistate Input objects, are available for the user program.
The AddMe Jr. BACnet IP server includes a Modbus RTU gateway for interfacing multiple Modbus devices to BACnet IP. Devices one may interface include VFD's, power monitors, etc.
• 12 Analog/universal inputs
• 0-10VDC, Thermistor, dry contact
• Software selectable input type
• 10-bit resolution
• 2 channels capable of pulse count input
• 2 Discrete outputs
• Open drain FET, 1A current sink
• 10/100BaseT Ethernet, BACnet IP
• Modbus RTU RS-485 Master gateway
• Data and event logger, email & trap notifications
• Real time scheduler including astronomical clock
• Web interface including user HTML wrapper
• User programmable via PL/i
• Powered by 18-30VDC or 24VAC 50/60 Hz
• Power Consumption: 0.3A @ 24VDC max.
• DIN rail mounting, 100mm H x 70mm W x 60mm D
• Pluggable screw terminal blocks
• Operating temperature -40°C to +85°C
• Humidity 5% to 90%
• FCC Class B, CE Mark
|
Click the web page image below to enter a demo copy of the actual web site contained within the (Modbus) Model AMJR-14.
BACnet is coming! Model AMJR-14-BN will be identical to this demo, except BACnet object mappings will replace Modbus register mappings.

Terminal block assignment for AddMe Jr.
|