Quick Help
The
source of data for a Multistate Input object will be reading the
remote Modbus register via the map indicated by the Device Link. The
Modbus device will be polled at the rate specified by the Read Map.
Out
of Service means polling of the Modbus register will stop. While out of
service, the present value may be written by the BACnet client. Data
may be forced via this web page at any time, but will be overwritten by
the next Modbus poll unless the object is out of service.
Reliability codes may be any of the following:
Modbus client, no response (64)
Modbus client, crc error (65)
Modbus exception, illegal function code (66)
Modbus exception, illegal data address (67)
Modbus exception, illegal data value (68)
Modbus exception, code+65, rarely used (69..79)
Local device, configuration property fault (80)
Faulty Modbus packet(81)
BACnet IP client, device timeout (82)
BACnet IP client, error returned by server (83)
Status flags A,B,C,D indicate the following, 0 meaning not true, 1 meaning true:
A = in alarm
B = fault
C = overridden
D = out of service
Device
link will indicate RTU or TCP, followed by R for read or W for write,
and a number which is the rule number in the table of read or write
rules for mapping Modbus to this BACnet object. The designation R means
read from Modbus, and W means write to Modbus.
|
|
|