This page displays BACnet IP port settings.
BACnet IP Settings:
Device Instance
Local Network Settings
Port (default 0xBAC0 = 47808)
Device Description
Device Location
Local Command Priority (default 10)
Quick Help

Enter a device instance from 1 to 4,194,303. Enter a port number (note that 47808 is the standard port expected by most BIP devices).

The description is the device property returned when Description, property ID 28, is read from the gateway. The location is the device property returned when Location, property ID 58, is read from the gateway.

Local command priority is the priority level that a commandable output object will assume when written locally by the scheduler or other action rules.

Click Save to store. This store process will take a little while as these parameters are being saved to non-volatile memory.