| Quick Help
Initial
COV increment and period will only apply if a BACnet client subscribes
to COV notification from the BACnet object assigned to this Modbus map.
These properties may be overwritten by the BACnet client(s) at any
time. The values shown here are initial values, not necessarily the
current values. (Note: COV increment only applies to Analog
objects, all changes are reported for Binary or Multistate objects.) Units
default to no_units, but you may select any of the available
BACnetEngineeringUnits values. This value will simply be read by
the BACnet client when the units property is requested from the
object this Modbus register maps to. The units have no bearing on
calculations performed. You must select appropriate scale and offset
values to make any required translation between input units
and BACnet units. Units are only valid for Analog objects;
however, the discrete inputs are treated as analog since they are most
often used for pulse counting or frequency measurement. |