AddMe III contains no configuration jumpers. There is no need to open the enclosure. Analog input types are switched between voltage and thermistor inputs under software control.

I/O points should be connected as indicated in the various diagrams below. In addition to selecting a wiring diagram, the corresponding selections should be made in the I/O Devices -> I/O Setup web pages to inform software of your intentions.

IMPORTANT: Save your configuration changes to the internal file system on the System -> Setup -> Config File page. Configuration will revert back to defaults upon the next power cycle if configuration changes are not saved.

I/O Point Type
Wiring Guide
Additional Information
A/UI Analog Input:
0-10VDC
Voltage Input
AI inputs 1-18 will accept voltage inputs of up to 10VDC. Voltages to 12VDC will be measured. Voltages to 24VDC will be tolerated, but measurement is internally limited to a reading of 12VDC.
A/UI Analog Input:
0-20mA
Current Input
AI inputs 1-18 will accept current inputs of 0-20mA with the addition of a 500 ohm 1/2 watt external resistor. A 500 ohm resistor will produce a 0-10VDC signal. A 250 ohm resistor may also be used to produce a 0-5VDC signal.
A/UI Analog Input:
Thermistor Input
A/UI inputs 1-16 will accept thermistors of 3k, 10k, or 20k ohms. Linearization via interpolation of a 56-point table is performed internally.
A/UI Discrete Input:
Discrete Voltage
A/UI inputs 1-16 may be connected as discrete voltage sensing inputs. Inputs up to 24VDC are tolerated, but threshold sensing only functions over the 0-10VDC range.
A/UI Discrete Input:
Dry Contact Closure to Ground
A/UI inputs 1-16 may be connected as discrete inputs sensing dry contact closure to ground. Internal excitation of 5V @ 1mA is provided.
Discrete Output:
Open Drain FET
Current Sinking
24VDC @1.0 Amp
DO outputs 1-2 are open drain, current sinking FET outputs rated at 24VDC @ 1.0Amp.
Power
Connect AC or +DC power to Power terminal. Connect common or -DC power to GND terminal. GND is common to all terminals labeled COM.
Power consumption is 2.4 watts, or 0.1A @ 24VDC.
Communications
Connect RS-485 network to NET+/- terminals. Do not connect LonWorks to NET+/- terminals.
Communication signals comply with EIA-485 standard.
Wiring Terminals
Screw terminals ratings are substantially in excess of any I/O point ratings.

Screw terminals are pluggable. They unplug from the unit in 12-position blocks. Any combination of smaller 5.00mm terminal blocks can optionally be used instead.