| I/O Point Type |
Wiring Guide | Additional Information |
A/UI Analog Input: 0-10VDC Voltage Input |
| AI
inputs 1-18 will accept voltage inputs of up to 10VDC. Voltages to
12VDC will be measured. Voltages to 24VDC will be tolerated, but
measurement is internally limited to a reading of 12VDC. |
A/UI Analog Input: 0-20mA Current Input |
| AI
inputs 1-18 will accept current inputs of 0-20mA with the addition of a
500 ohm 1/2 watt external resistor. A 500 ohm resistor will produce a
0-10VDC signal. A 250 ohm resistor may also be used to produce a
0-5VDC signal. |
A/UI Analog Input: Thermistor Input |
| A/UI inputs
1-16 will accept thermistors of 3k, 10k, or 20k ohms. Linearization via
interpolation of a 56-point table is performed internally. |
A/UI Discrete Input: Discrete Voltage |
| A/UI inputs
1-16 may be connected as discrete voltage sensing inputs. Inputs up to
24VDC are tolerated, but threshold sensing only functions over the
0-10VDC range. |
A/UI Discrete Input: Dry Contact Closure to Ground |
| A/UI inputs
1-16 may be connected as discrete inputs sensing dry contact closure to
ground. Internal excitation of 5V @ 1mA is provided. |
Discrete Output: Open Drain FET Current Sinking 24VDC @1.0 Amp |
| DO outputs 1-2 are open drain, current sinking FET outputs rated at 24VDC @ 1.0Amp. |
| Power |
Connect
AC or +DC power to Power terminal. Connect common or -DC power to
GND terminal. GND is common to all terminals labeled COM. |
Power consumption is 2.4 watts, or 0.1A @ 24VDC. |
| Communications |
Connect RS-485 network to NET+/- terminals. Do not connect LonWorks to NET+/- terminals. |
Communication signals comply with EIA-485 standard. |
| Wiring Terminals |
| Screw terminals ratings are substantially in excess of any I/O point ratings.
Screw
terminals are pluggable. They unplug from the unit in 12-position
blocks. Any combination of smaller 5.00mm terminal blocks can
optionally be used instead. |