The
values of analog inputs are updated each time you click "update".
Register data is produced by applying respective slope and intercept to
raw data read from hardware. Change input type and scale factors in I/O
Setup->Analog Inputs. The
nature of data displayed will depend on channel configuration. In most
cases, the integer data (Int Data) will be the raw counts from the
A/D converter. If a thermistor input is selected, integer data will be
linearized degrees times 100. If discrete input is selected, the
integer (raw data) value will be either 0 or 1. Floating
point data will reflect degrees (C or F) when configured for
thermistor input. Voltage readings will be normalized to 10.0 volts.
Discrete readings will be 0 or 10. In all instances, slope and
intercept are applied after linearization or normalization. Therefore
the displayed data may not necessarily be in the range of 0 to 10.0. It
can be scaled to any engineering units range. The
inputs displayed on this page may be read via Modbus or SNMP. The
Modbus holding register number is shown in the first column.
SNMP OID's are a prefix with this register number added on. |