Analog outputs are generated by an 8-bit D/A converter. Therefore, the raw data applied must be in the range of 0..255. The raw count may be written directly to the integer register corresponding to the output. If floating point data representing engineering units is written to the corresponding floating point register, this will be converted to raw data using the slope and intercept provided.

These physical inputs correspond to BACnet AO objects starting at #1.

Slope: Scales floating point data to calculate raw binary data for output.

Intercept: Offsets floating point data to calculate raw binary data for output.

AO#: Enter a number or use up/down arrows to scroll through the available analog output objects.