The discrete outputs are turned on or off by the value of the integer register assigned to the output. A zero turns the output off, while any non-zero value turns the output on. Floating point data is simply converted to integer and copied to the corresponding integer register when a floating point value is written.

These physical inputs correspond to BACnet BO objects starting at #1.

Optional Timer: Select No Timer, Pulsed Output, or Min Time Qualified. When pulsed, writing a nonzero value to the register will turn the output on for the amount of time given as "period". When Min Time Qualified, the output must remain in the same state for this minimum amount of time before it will be allowed to switch to the opposite state.

Period: This time in tenths of seconds applies to pulsed output or min time qualified. See timer selection above.

DO#: Enter a number or use up/down arrows to scroll through the available discrete output objects.