| I/O Point Type |
Wiring Guide
|
Additional Information |
A/UI Analog Input:
0-10VDC
Voltage Input |
|
AI inputs 1-12 will accept voltage inputs of up to 10VDC. Voltages to 12VDC will be measured. Voltages to 24VDC will be tolerated, but measurement is internally limited to a reading of 12VDC. |
A/UI Analog Input:
0-20mA
Current Input |
|
AI inputs 1-12 will accept current inputs of 0-20mA with the addition of a 500 ohm 1/2 watt external resistor. A 500 ohm resistor will produce a 0-10VDC signal. A 250 ohm resistor may also be used to produce a 0-5VDC signal. |
A/UI Analog Input:
Thermistor Input |
|
A/UI inputs 1-12 will accept thermistors of 3k, 10k, or 20k ohms. Linearization via interpolation of a 56-point table is performed internally. |
A/UI Discrete Input:
Discrete Voltage |
|
A/UI inputs 1-12 may be connected as discrete voltage sensing inputs. Inputs up to 24VDC are tolerated, but threshold sensing only functions over the 0-10VDC range. |
A/UI Discrete Input:
Dry Contact Closure to Ground |
|
A/UI inputs 1-12 may be connected as discrete inputs sensing dry contact closure to ground. Internal excitation of 5V @ 1mA is provided.
Recommended software settings: Dry Contact, Inverted, Threshold = 50%.
Voltage present will generate a binary 1. A closure to ground will force voltage to zero. Therefore, "inverted" will generate a binary 1 when the contact is closed resulting in zero volts present at the input.
|
Discrete Output:
Open Drain FET
Current Sinking
24VDC @1.0 Amp |
|
DO outputs 1-2 are open drain, current sinking FET outputs rated at 24VDC @ 1.0Amp. |
| Power |
Connect AC or +DC power to Power terminal. Connect common or -DC power to GND terminal. GND is common to all terminals labeled COM.
|
Power consumption is 2.4 watts, or 0.1A @ 24VDC.
|
| Communications |
Connect RS-485 network to NET+/- terminals.
|
Communication signals comply with EIA-485 standard.
|
| Wiring Terminals |
|
Screw terminals ratings are substantially in excess of any I/O point ratings.
Screw terminals are pluggable. They unplug from the unit in 12-position blocks. Any combination of smaller 5.00mm terminal blocks can optionally be used instead.
|