Standard Object Properties:
|
| Object_Identifier (75) |
BACnetObjectIdentifier |
| Object_Name (77) |
CharacterString
“Analog Value n”
|
| Object_Type (79) |
BACnetObjectType
ENUMERATED: analog-input (0)
analog-value (2)
binary-input (3)
binary-value (5)
device (8)
|
| Present_Value (85) (W) |
REAL
(no index)
|
| Status_Flags (111) |
BACnetStatusFlags
BIT STRING: fault(1), out-of-service(3)
|
| Event_State (36) |
BACnetEventState
ENUMERATED: normal(0), fault(1)
|
| Reliability (103) |
BACnetReliability
ENUMERATED: normal(0)
Vendor specific:
no response, device query fail (64)
no response, NV fail (67)
configuration property fault (80)
|
| Out_Of_Service (81) (W) |
BOOLEAN |
| Priority_Array (87) |
BACnetPriorityArray
SEQUENCE SIZE (16) OF BACnetPriorityValue
REAL (each element)
|
| Relinquish_Default (104) (W) |
REAL |
| Units (117) |
BACnetEngineeringUnits |
|
Vendor Specific Object Properties:
|
| Object_Map_Use (701) (W) |
BIT STRING:
(1) map enabled
(2) NV direction, 0=NVO at remote, 1=NVI at remote
(3) grouped - object is field in NV struct
(4) lock - this field triggers NV struct update |
| Special_Service_Request (702) (W) |
BIT STRING:
(1) default to out of service at power-up
(2) invoke write at power-up if writeable object
(3) set BACnet Present Value to default if Lon communication fails
|
| Node_Index (703) (W) |
ENUMERATED
(1..20) selects LonWorks device mapped to this object
|
| NV_Index (704) (W) |
Unsigned
NV index within device (0..61)
|
| SNVT_Index (705) (W) |
OCTET STRING (size 4):
(1) SNVT index, 0=raw data
(2) NVT_CAT if raw
(3) Byte offset if raw
(4) Bit offset if raw
|
| Scale_Array (706) (W) |
Integer:
Index 1..3
(1) Scale A
(2) Scale B
(3) Scale C
|
| Default_Value (707) (W) |
REAL |
| Reference_String (708) (W) |
CharacterString |